Getting started with tank monitoring

1

.

Introduction

This tank monitoring manual contains step-by-step instructions for installing, setting up and troubleshooting common problems.

2

.

Check what type of gateway you have

There are several gateway types in our range, using the options below you can follow detailed steps.

Digital Matter Hawk, Digital Matter Falcon, Digital Matter Eagle

3

.

Calibration of the depth sensor

Calibrate the depth sensor after installing it in the tank to make the best use of the monitoring.

To correctly calibrate the depth sensor the tank must be completel filled. Should this not be possible you can contact us.

Modify the metadata “Tank100pct” and enter the 4-20mA value here from when the tank was completely full.

Please note! The tank monitor sends its data every hour, wait until you are sure it is the highest value.

When you have customized your metadata you can use the path “tank_level,” this path is percentage based.

Need Support?

Can’t find the answer you’re looking for? Don’t worry we’re here to help!

Ask For Help
Language Choice Disclaimer

These texts have been automatically translated using advanced AI translation tools. If you notice any inaccuracies or errors, please help us improve by sending a message to hello@calculus.group. Your feedback assists us in enhancing the quality of our multilingual documentation.