How to set a firing protocol?
1
.
Requirements
- U have the "Scheduling" user right.
- You have
taken note of the following standards:
NEN-EN 1264-2:2008+A1:2012
DIN EN 1264-4. -
We
recommend that you review the articles below so that you are well prepared
for this manual.
tasks set in the scheduler
2
.
Standards used
Below is an overview of the heating protocols used, their schedules and the necessary settings for the actions in the scheduler:
NEN-EN 1264-2:2008+A1:2012
Day |
Schedule type |
Action definition
|
Value
| Color Task
|
Day 1
|
Execute Action
|
Setpoint temperature start burner1 |
20 | Green: #1ED828 |
Execute Action
| Floor heating status | 1 |
Green: #1ED828 | |
Day 2
|
Execute Action |
Setpoint temperature start burner1 |
25 | Orange: #EC7B11 |
Day 3 |
Execute Action |
Setpoint temperature start burner1 |
30 | Orange: #EC7B11 |
Day 4 |
Execute Action |
Setpoint temperature start burner1 |
35 | Orange: #EC7B11 |
Day 5 |
Execute Action |
Setpoint temperature start burner1 |
40 | Orange: #EC7B11 |
Day 6 |
Execute Action |
Setpoint temperature start burner1 |
40 | Orange: #EC7B11 |
Day 7
|
Execute Action | Setpoint temperature start burner1 | 35 | Orange: #EC7B11 |
Day 8
|
Execute Action | Setpoint temperature start burner1 | 30 | Orange: #EC7B11 |
Day 9
|
Execute Action | Setpoint temperature start burner1 | 25 | Orange: #EC7B11 |
Day 10
|
Execute Action | Setpoint temperature start burner1 | 20 | Orange: #EC7B11 |
Day 11
|
Execute Action | Setpoint temperature start burner1 | 0 | Red: #EC2A11 |
Execute Action | Floor heating status | 3 |
Red: #EC2A11 | |
Execute Action
| Floor heating status | 0 |
Red: #EC2A11 |
DIN EN 1264-4 8 days
Day |
Schedule type |
Action definition
|
Value
| Color Task |
Day 1 |
Execute Action
|
Setpoint temperature start burner1 |
25 | Green: #1ED828 |
Execute Action
| Floor heating status | 1 |
Green: #1ED828 | |
Day 2 |
Execute Action
|
Setpoint temperature start burner1 |
25 | Orange: #EC7B11 |
Day 3 |
Execute Action
|
Setpoint temperature start burner1 |
25 | Orange: #EC7B11 |
Day 4 |
Execute Action
|
Setpoint temperature start burner1 |
50 | Orange: #EC7B11 |
Day 5 |
Execute Action
|
Setpoint temperature start burner1 |
50 | Orange: #EC7B11 |
Day 6 |
Execute Action
|
Setpoint temperature start burner1 |
50 | Orange: #EC7B11 |
Day 7
|
Execute Action
| Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 8
|
Execute Action
| Setpoint temperature start burner1 | 0 | Red: #EC2A11 |
Execute Action
| Floor heating status | 3 |
Red: #EC2A11 | |
Execute Action | Floor heating status | 0 |
Red: #EC2A11 |
DIN EN 1264-4 20 days
Day |
Schedule type |
Action definition
|
Value
| Color Task |
Day 1 |
Execute Action |
Setpoint temperature start burner1 |
25 | Green: #1ED828 |
Execute Action | Floor heating status | 1 |
Green: #1ED828 | |
Day 2 |
Execute Action |
Setpoint temperature start burner1 |
30 | Orange: #EC7B11 |
Day 3 |
Execute Action |
Setpoint temperature start burner1 |
35 | Orange: #EC7B11 |
Day 4 |
Execute Action |
Setpoint temperature start burner1 |
40 | Orange: #EC7B11 |
Day 5 |
Execute Action |
Setpoint temperature start burner1 |
45 | Orange: #EC7B11 |
Day 6 |
Execute Action |
Setpoint temperature start burner1 |
50 | Orange: #EC7B11 |
Day 7
|
Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 8
|
Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 9
|
Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 10
|
Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 11 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 12 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 13 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 14 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 15 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 16 | Execute Action | Setpoint temperature start burner1 | 50 | Orange: #EC7B11 |
Day 17 | Execute Action | Setpoint temperature start burner1 | 45 | Orange: #EC7B11 |
Day 18 | Execute Action | Setpoint temperature start burner1 | 35 | Orange: #EC7B11 |
Day 19 | Execute Action | Setpoint temperature start burner1 | 25 | Orange: #EC7B11 |
Day 20
|
Execute Action | Setpoint temperature start burner1 | 0 | Red: #EC2A11 |
Execute action | Floor heating status | 3 |
Red: #EC2A11 | |
Execute Action | Floor heating status | 0 |
Red: #EC2A11 |
3
.
Een opstookprotocol instellen op het Calculus portaal
Open the Calculus portal and go through the navigation menu to the scheduler.
It always opens on the current date and is highlighted in green. You can use the date selection at the top left to go to the desired date. Then double-click on the time you want to schedule an action to schedule an action.
You are now in the "Schedule" panel.
Give this action a title (for example, "Day 1"). Verify that the start date/time is correct and set the repeat to "Never".
Give the action a color. Which color to use on which day should be used can be found in the tables above.
For the planning type, choose "Execute action" and for the execution rule for "Only Last".
As the asset type, select "Thermobile boiler," and as the asset the specific boiler for which you want to use the heating protocol (in this example, "11438-0025 Boiler 165 kW").
As the action definition, select "Setpoint temperature start burner 1." As the value, enter the number found in the table above.
On some days, multiple actions must be performed. U can add a new action by clicking the "Add" button, above the "ExecuteAction" box.
Finally, click "Save" and repeat the above steps for each day in the table.