Meaning LEDs on C07W?
1
.
Introduction
The C07 has 5 LEDs on the front panel that indicate the status of the gateway:
2
.
Power
Indicates the status of the power supply.
Green (continuous): the power supply of the C07W gateway is OK.
Off: the internal components of the C07W are not powered.
You can try the following:
- Check that the power supply is properly connected to an outlet;
- Check the wiring from the power supply to the C07W;
- Check the output voltage of the power supply (the power supply may be damaged);
- The internal fuse of the C07W may have blown due to overcurrent and should be replaced by Calculus.
3
.
Status
General status of the gateway.
Green (flashing): the C07W is booting up.
Green (continuous): the C07W has finished booting up and is running normally.
4
.
Connected
Connection strength to the cloud.
Red (continuous): the connection of the C07W to the cloud is broken.
Red (flashing): the C07W is not connected, and is waiting for an Internet connection.
Green (flashing): the C07W is connected to the cloud and is trying to synchronize its internal clock.
Green (continuous): the C07W is connected to the cloud with a synchronized clock.
Orange (pulsing): a measurement or event is being sent to the cloud.
5
.
Expansion 1 & 2
Status of expansion card in slot 1 & 2.
The LED indicators vary by expansion card:
- Modbus
- LoRa
- LTE Modem
The following section describes the most relevant indicators.
Red (continuous): the C07W has detected an expansion card and is booting it.
Red (flashing): there is an error has occurred on the expansion card.
LTE modem
Red: the modem has no internet connection.
Orange (flashing): the modem is not yet registered in the mobile network, but is trying to register (0.5 seconds orange / 0.5 seconds red).
Orange (pulsing): the modem is successfully registered in the mobile network, but does not yet have an internet connection (0.3 seconds orange / 2.7 seconds red).
Green (pulsing): the modem is connected to the internet (0.3 seconds red / 2.7 seconds off).
Modbus RTU+
Off: normal operation.
LoRa concentrator
Off: normal operation, has yet to receive a LoRa packet in the current session.
Green (flashing): LoRa packet received
Green (continuous): normal operation, at least 1 LoRa packet received in the current session.