Setting Eastron SDM630MCT-ML
1
.
Focus areas
- Check that the energy meter is properly connected to the CT (current transformer) before configuring it.
- The white wire / S1 of the transformer should be connected to the + terminal of the energy meter.
- The black wire / S2 of the transformer should be connected to the - terminal of the energy meter.
- Caution: if connected improperly, there is the possibility that the current will be measured incorrectly. For example: When you connect the black wire to the positive terminal of the energy meter.
- See also the following section in the Eastron energy meters manual - installing a CT.
2
.
Open the settings
To access the settings, press
for 3 seconds until the password screen is visible.
The default password is "1000. Enter the password using the up and down buttons:
and
If the password is different, you can navigate to the other numbers by pressing the E button once. You can then adjust them with the M and P buttons .
Press
for 3 seconds to confirm the password.
Any change in the settings is saved by holding down the E button for 3 seconds.
If the password is correct you will enter the slave id menu by default.
3
.
Changing slave id
Set communication address. Press
| |
Communication address modes (quantity) setting interface | The meter has two communication address modes: 1. Single communication address: there is only 1 address for the whole meter and all channels use the same communication address. 2. Multiple communication addresses: there are 4 or 3 or 2 different communication addresses for different channels. |
Setting interface for communication address mode. Press and hold
| |
Press Option: 1, M* (default) 1 means one communication address mode; M* means multiple communication addresses. It can be 2 or 3 or 4. It depends on the meter you have for double loads, triple loads or quadruple loads. Address setting, range 001~247 (One communication address mode) |
Address setting, range 001~247 (One communication address mode)
Set communication address. Press
| |
Press |
Address setting, range 001~247 (Multiple communication address mode)
Address setting for the corresponding channel. Press
| |
Press |
4
.
Setup CT clamp
Press
| |
Press
| |
Select the phase to be configured. Press
| |
CT1 settings interface. Press
|
To avoid errors in energy measurement, the P1 port of the CT should be pointed toward the power supply. However, if the P2 port is facing the power supply, you can still use the energy meter settings to correct it.
5
.
SDM630MCT-ML_Datasheet
6
.
SDM630MCT-ML_User_manual