Setup Eastron SDM54-2T

1

.

Start-up screen

When the energy meter starts up, you will see the following on the display:

After a short waiting period, the screen will show active energy readings.

Under the display of the energy meter there are 2 buttons. Their operation is as follows:

Scrolling through display for various parameters, changing options in set-up mode, exiting set-up mode.

Go to set-up mode, confirm a selection.

With each press of other parameters can be displayed.

A complete list of all possible parameters of your energy meter can be found in the Appendix.

2

.

Set-up

Press and holdfor about three seconds.

A password is required. This is 1000 by default. After entering the password, press

In the set-up menu, you will see the choices Main, Communication, Time and Pulse. Make your choice withand confirm with

In system type, you will see the network type where the meter is operational. The options are: 3P4W, 3P3W, 1P3W and 1P2W. Default is 3P4W.

After selection, the password appears and the first digit starts flashing. To change the value of the digit pressThen pressto confirm. Once you have done this with the 4 digits, the adjustment is confirmed.

Push reset to reset the maximum of current (DMD) , active power (DMD) and digital input counts (DI).

In the Com menu, you can set the communication parameters.

At Addr, set the modbus address (001 ~ 247). At Baud set the baud rate: 2400 ~ 38400bps. Default is 9600 bps. Parity gives parity options: None, Even and Odd. Default is None. Stop specifies the number of stop bits: 1 or 2. Default is 1 stop bit.

Time-related settings.

Backlight sets the time that the screen stays lit when the user has made an entry or after the display has been activated. Options: on, off, 5, 10, 15, 30, 60 and 120 minutes. Default is 60 minutes.

Use the scroll key to set the time interval at which to switch between requested information. Options: off, 5, 10, 15, 30, 60 seconds.

DMD selects the time interval at which the highest consumption in the previous period is displayed. Options: 0, 5, 8, 10, 15, 20, 30, 60 minutes. Default is 60 minutes.

Pulse output 1 parameter settings. Meter pulse 1 can be set. Pulse output 2 is fixed.

Type indicates the type of energy to which the pulse output refers. Options: kWh, Imp-kWh, Exp-kWh, kVarh, Imp-kVarh, Exp-kVarh. Default is Exp-kWh.

Constant gives the pulse output constant. It gives the amount of energy consumption, which is equal to a pulse generated by the meter. Options: 1000, 100, 10, 1. Default is 400.

Width gives pulse width options, or the length of time in which the most recent pulse is most active. Options: 60, 100, 200 mS. Default is 100 mS.