Setup Eastron SDM54-2T
1
.
Start-up screen
When the energy meter starts up, you will see the following on the display:
After a short waiting period, the screen will show active energy readings.
Under the display of the energy meter there are 2 buttons. Their operation is as follows:
Scrolling through display for various parameters, changing options in set-up mode, exiting set-up mode.
Go to set-up mode, confirm a selection.
With each press of other parameters can be displayed.
A complete list of all possible parameters of your energy meter can be found in the Appendix.
2
.
Set-up
Press and holdfor about three seconds.
A password is required. This is 1000 by default. After entering the password, press | |
In the set-up menu, you will see the choices Main, Communication, Time and Pulse. Make your choice withand confirm with
| |
In system type, you will see the network type where the meter is operational. The options are: 3P4W, 3P3W, 1P3W and 1P2W. Default is 3P4W.
| |
After selection, the password appears and the first digit starts flashing. To change the value of the digit pressThen pressto confirm. Once you have done this with the 4 digits, the adjustment is confirmed.
| |
Push reset to reset the maximum of current (DMD) , active power (DMD) and digital input counts (DI).
| |
In the Com menu, you can set the communication parameters.
| |
At Addr, set the modbus address (001 ~ 247). At Baud set the baud rate: 2400 ~ 38400bps. Default is 9600 bps. Parity gives parity options: None, Even and Odd. Default is None. Stop specifies the number of stop bits: 1 or 2. Default is 1 stop bit.
| |
Time-related settings.
| |
Backlight sets the time that the screen stays lit when the user has made an entry or after the display has been activated. Options: on, off, 5, 10, 15, 30, 60 and 120 minutes. Default is 60 minutes. Use the scroll key to set the time interval at which to switch between requested information. Options: off, 5, 10, 15, 30, 60 seconds. DMD selects the time interval at which the highest consumption in the previous period is displayed. Options: 0, 5, 8, 10, 15, 20, 30, 60 minutes. Default is 60 minutes.
| |
Pulse output 1 parameter settings. Meter pulse 1 can be set. Pulse output 2 is fixed.
| |
Type indicates the type of energy to which the pulse output refers. Options: kWh, Imp-kWh, Exp-kWh, kVarh, Imp-kVarh, Exp-kVarh. Default is Exp-kWh. Constant gives the pulse output constant. It gives the amount of energy consumption, which is equal to a pulse generated by the meter. Options: 1000, 100, 10, 1. Default is 400. Width gives pulse width options, or the length of time in which the most recent pulse is most active. Options: 60, 100, 200 mS. Default is 100 mS.
|
Was this article helpful?