How to set a firing protocol?

1

.

Requirements

  • U have the "Scheduling" user right.
  • You have taken note of the following standards:
    NEN-EN 1264-2:2008+A1:2012
    DIN EN 1264-4.
  • We recommend that you review the articles below so that you are well prepared for this manual.
    tasks set in the scheduler

2

.

Standards used

Below is an overview of the heating protocols used, their schedules and the necessary settings for the actions in the scheduler:

NEN-EN 1264-2:2008+A1:2012

Day

Schedule type

Action definition

Value

Color Task

Day 1

Execute Action

Setpoint temperature start burner1

20

Green: #1ED828


Execute Action

Floor heating status

1

Green: #1ED828

Day 2

Execute Action

Setpoint temperature start burner1

25

Orange: #EC7B11

Day 3

Execute Action

Setpoint temperature start burner1

30

Orange: #EC7B11

Day 4

Execute Action

Setpoint temperature start burner1

35

Orange: #EC7B11

Day 5

Execute Action

Setpoint temperature start burner1

40

Orange: #EC7B11

Day 6

Execute Action

Setpoint temperature start burner1

40

Orange: #EC7B11

Day 7

Execute Action

Setpoint temperature start burner1

35

Orange: #EC7B11

Day 8

Execute Action

Setpoint temperature start burner1

30

Orange: #EC7B11

Day 9

Execute Action

Setpoint temperature start burner1

25

Orange: #EC7B11

Day 10

Execute Action

Setpoint temperature start burner1

20

Orange: #EC7B11

Day 11

Execute Action

Setpoint temperature start burner1

0

Red: #EC2A11


Execute Action

Floor heating status

3

Red: #EC2A11


Execute Action 

Floor heating status

0

Red: #EC2A11


 

DIN EN 1264-4 8 days

Day

Schedule type

Action definition

Value

Color Task

Day 1

Execute Action 

 

Setpoint temperature start burner1

25

Green: #1ED828


Execute Action 

 

Floor heating status

1

Green: #1ED828

Day 2

Execute Action 

 

Setpoint temperature start burner1

25

Orange: #EC7B11

Day 3

Execute Action 

 

Setpoint temperature start burner1

25

Orange: #EC7B11

Day 4

Execute Action 

 

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 5

Execute Action 

 

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 6

Execute Action 

 

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 7

Execute Action 

 

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 8

Execute Action 

 

Setpoint temperature start burner1

0

Red: #EC2A11


Execute Action 

 

Floor heating status

3

Red: #EC2A11


Execute Action

Floor heating status

0

Red: #EC2A11



 

DIN EN 1264-4 20 days

Day

Schedule type

Action definition

Value

Color Task

Day 1

Execute Action

Setpoint temperature start burner1

25

Green: #1ED828


Execute Action

Floor heating status

1

Green: #1ED828

Day 2

Execute Action

Setpoint temperature start burner1

30

Orange: #EC7B11

Day 3

Execute Action

Setpoint temperature start burner1

35

Orange: #EC7B11

Day 4

Execute Action

Setpoint temperature start burner1

40

Orange: #EC7B11

Day 5

Execute Action

Setpoint temperature start burner1

45

Orange: #EC7B11

Day 6

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 7

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 8

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 9

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 10

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 11

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 12

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 13

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 14

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 15

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 16

Execute Action

Setpoint temperature start burner1

50

Orange: #EC7B11

Day 17

Execute Action

Setpoint temperature start burner1

45

Orange: #EC7B11

Day 18

Execute Action

Setpoint temperature start burner1

35

Orange: #EC7B11

Day 19

Execute Action

Setpoint temperature start burner1

25

Orange: #EC7B11

Day 20

Execute Action

Setpoint temperature start burner1

0

Red: #EC2A11


Execute action

Floor heating status

3

Red: #EC2A11


Execute Action

Floor heating status

0

Red: #EC2A11



3

.

Een opstookprotocol instellen op het Calculus portaal

Open the Calculus portal and go through the navigation menu to the scheduler.

It always opens on the current date and is highlighted in green. You can use the date selection at the top left to go to the desired date. Then double-click on the time you want to schedule an action to schedule an action.

You are now in the "Schedule" panel. 


Give this action a title (for example, "Day 1"). Verify that the start date/time is correct and set the repeat to "Never".

Give the action a color. Which color to use on which day should be used can be found in the tables above.


For the planning type, choose "Execute action" and for the execution rule for "Only Last".


As the asset type, select "Thermobile boiler," and as the asset the specific boiler for which you want to use the heating protocol (in this example, "11438-0025 Boiler 165 kW").


As the action definition, select "Setpoint temperature start burner 1." As the value, enter the number found in the table above.


On some days, multiple actions must be performed. U can add a new action by clicking the "Add" button, above the "ExecuteAction" box.

Finally, click "Save" and repeat the above steps for each day in the table.

    Related Articles

Need Support?

Can’t find the answer you’re looking for? Don’t worry we’re here to help!

Ask For Help
Language Choice Disclaimer

These texts have been automatically translated using advanced AI translation tools. If you notice any inaccuracies or errors, please help us improve by sending a message to hello@calculus.group. Your feedback assists us in enhancing the quality of our multilingual documentation.